Unit 214 — AC blowing warm air
CompletedJob #24041•HVAC · Repair•Larkspur Property Group
- RequestOct 19
- EstimateNot required
- Approved—
- ScheduledOct 20
- In progressStarted
- CompletedOct 20
- 7Invoiced#10489
- 8Paid
Description
Tenant in Unit 214 reports warm air from all vents since Sunday evening. 3-ton split system, 2018. Outdoor fan reported not spinning.
- Scheduled
- Tuesday, October 207:30 AM – 9:30 AM
- Assigned to
- Carlos Rivera
- Estimated value
- $685
- Service address
- 1420 Marina Shores DrClearwater, FL 33755
- Source
- Phone
- Created
- Oct 19, 4:12 PM
Equipment on file
Notes
- Carlos Rivera28m ago
Run capacitor failed (bulged, reading 18 µF on a 45 µF rating). Replaced capacitor and pitted contactor. Supply 56°F / return 76°F. Tenant signed off.
Job timeline
Every step recorded automatically
Service request received by phone
Oct 19 · 4:12 PM · Priya Desai
Scheduled for Tue, Oct 20 · 7:30 AM
Oct 19 · 4:20 PM · Priya Desai
Assigned to Carlos Rivera
Oct 20 · 7:05 AM · Priya Desai
Technician en route
Oct 20 · 7:08 AM · Carlos Rivera
Technician arrived on site
Oct 20 · 7:31 AM · Carlos Rivera
3 photos uploaded
Oct 20 · 9:10 AM · Carlos Rivera
Customer signed work order
Oct 20 · 9:19 AM · Tenant, Unit 214
Work completed
Oct 20 · 9:20 AM · Carlos Rivera
Invoice #10489 generated automatically
Oct 20 · 9:21 AM · FieldFlow
Customer
- (727) 555-0124
- dkim@larkspurpg.example
- 1420 Marina Shores DrClearwater, FL 33755
Check in with on-site manager, Unit 101.